•Membrane panel
•Alarm and error LEDs for each zone
•24V battery voltage
•Alarm and error relays (NO,NC,COM)
•Contact output
•External 24V output can supply power to 5 gasdetectors
•Alarm and error verification in 5 seconds
•Earthing error detection
•Mains power status warning LED
•Battery error LED
•Siren output monitoring and warning
•Deactivatable zones
•Ability to set delay to alarm output
•Testable by one person
• Produced with surface
PRODUCT CODE: M.U.YAN.00005Mains input voltage 230V AC 50 Hz
Operating voltage 24V DC
Battery 2 units 12V DC 4Ah
Battery charging current Max. 0.5A
Battery fuse 0.5A
SMPS power supply output 2.5A
Siren outputs 2 units 24V 0.5A capacity, glass fuse protection
Auxiliary 24V output 24V 0.5A capacity, glass fuse protection
Fire alarm relay output 1A 120VAC / 2A 24VDC
Error alarm relay output 1A 120VAC / 2A 24VDC
System fuse 4A glass fuse
Heat detector capacity per 16 zone
Smoke detector capacity per 16 zone
Manual call point capacity Unlimited
per zone End of line resistance
For conventional zone : 4K7 1/4W, for siren line 4K7 1/4W
Number of zones 4-8-16 zones
Dimensions 31.5 x 32.5 x 11.5cm
Operating temperature -10°C / +55°C
Humidity Up to %95
Type of mounting Surface Type
Cable entry Top